On/Off valve with float control DN 125 PN 10/16On/Off valve with float control DN 125 PN 10/16

1600125000 On/Off valve with float control DN 125 PN 10/16

Components

  • 1: Main valve
  • 2: Ball valve
  • 3: Filter
  • 4: Throttle check valve
  • 5: Control valve
  • 6: Float
  • 7: Float protection pipe (optional)
  • 8: Opening limiter
  • 9: Pressure gauge with ball valve
Add to watchlist
Product attributes
DN 125
PN 16 bar
L 400 mm
B1 200 mm
B2 210 mm
H1 390 mm
H2 500 mm
KVS
l/min.
2955
weight 50.600 kg
NPK No.
411
834221
BIM /
CAD
Availability on demand

Physical characteristics

  • The main valve is a hydraulically operating diaphragm valve. The work energy is the inherent medium.
  • Most valve types operate purely hydraulically without any foreign energy.

Application

  • To use in drinking water systems (other media after consultation)
  • Level control in a reservoir or pressure–breaking shaft
  • Level control in an equalising basin

Mode of operation

  • The open/close valve with float protection mechanically/hydraulically regulates the water inflow in a reservoir by means of a float solenoid valve and float bulbs. The closing speed can be adjusted by means of a throttle non–return valve to prevent surges in pressure.
  • At inlet pressures less than 1.5 bar and more than 4 bar consultation is to be kept.

Product information

  • To calculate the dimensions of the valve please refer to the following information:
  • Maximum and minimum inlet pressure (static and dynamic pressure ratios)
  • Existing counterpressure of the reservoir
  • Required flow rate
  • Available line diameters and lengths
  • Construction of the valve (straight or angle design)
  • Minimum and maximum water level (as standard between 100 and 900 mm can be adjusted using stops, greater water level differences on request)
  • For the calculation basis, information on the loss of pressure and the characteristic values of the valve, please refer to the end of Chapter E.

Design

  • Design according to DIN EN 1074
  • Construction length acc. to DIN EN 558
  • Flange mass according to DIN 1092-2, to PN 25 DN 300
  • Pressure levels: PN 10 or PN 16 to DN 300, PN 25 to DN 200, higher pressures on request.
  • Nominal widths DN 50, DN 80, DN 100 and DN 150 available in angular design
  • Nominal widths 1 ½" and 2" with threaded connection (female thread)
  • Medium temperature up to 40°C

Installation and assembly

  • Shut–off valves should be fitted on both sides of the valve and a dirt trap should be installed on the inlet side of the valve. Depending on the installation situation, a mounting/dismounting adapter should be provided. If there is a free run into the water tank downstream from the valve, the slider on the outlet side can be omitted. Depending on the pressure ratios, an orifice plate should be installed on the outlet side of the valve and an opening limiter on the valve. The installation of a float protection pipe is recommended to guide the float.

Vantages

  • Maintenance-free, non-rusting valve seat
  • Pressed-in seat
  • EWS-coating according to RAL GSK

Caution

  • Dimension H1 with electric position indicator and opening limiter is 110 mm higher up to DN 100 and 130 mm higher at DN 125 to DN 300.
more